Current sensor

CSO 38

CSO 38 sensor is a current transformer load is less than 2 VA. The secondary current is 1 A. The output cable length 12 m (length can be customized), the outer insulation is from silicone rubber. The accuracy of conversion depends on the required load.

The sensor is designed for outdoor environments with the highest pollution (ie. 31 mm/kV to 38.5 kV).

Current sensor complies with IEC 60044-1 and GOST 15 150 for T1 and UCHL1.

Other technical parameters can be consulted with the manufacturer.

Inquire

Description

CSO 38 sensor is a current transformer load is less than 2 VA. The secondary current is 1 A. The output cable length 12 m (length can be customized), the outer insulation is from silicone rubber. The accuracy of conversion depends on the required load.

The sensor is designed for outdoor environments with the highest pollution (ie. 31 mm/kV to 38.5 kV).

Current sensor complies with IEC 60044-1 and GOST 15 150 for T1 and UCHL1.

Other technical parameters can be consulted with the manufacturer.

Read more

Parameters

  • Highest voltage for equipment: 36/38.5 kV
  • Power frequency test voltage: 70/80 kV
  • Lightning impulse test voltage: 170/180 kV
  • Nominal primary current: 50–200 A
  • Nominal secondary current: 1 A
  • Rated short-time thermal current, Ith: 12.5 kA
  • Rated dynamic current, ldyn: 31.5 kA
  • Accuracy class - protection: 2–3 %
  • Overcurrent factor - measurement: FS5 for 50 A, for the higher currents>5
  • Nominal power: 2 VA
  • Nominal frequency: 50 Hz
  • Weight: 11 kg
  • Thermal insulation class: E
  • Operation conditions: corresponds to temperature class -5/40 according to IEC 61869-1
  • Standard: ČSN EN 60044-1, IEC EN 60044-1, ČSN EN 61869-1, ČSN EN 61869-2, IEC EN 61869-1, IEC EN 61869-2, GOST 15 150