Current instrument supporting transformer

CTSO 38L

Current instrument supporting transformer CTSO 38L is designed for measurement and protection of high voltage distributing equipment for outdoor design for nominal primary currents of 5-2500 A and for the highest voltage of system of 38.5 kV.

The value of secondary current is 5 A or 1 A with the possibility of combination.

The accuracy classes for the circuits of measurement are 0.2, 0.2S, 0.5, 0.5S, 1, 3, for the circuits of protection are 5P, 10P. The transformers fulfill the required accuracy class at intervals from 25 % to 100 % of rated load.

Inquire

Parameters

  • Highest voltage for equipment: 36/38.5 kV
  • Power frequency test voltage: 70/80 kV
  • Lightning impulse test voltage: 170/180 kV
  • Nominal primary voltage: 5–2500 A
  • Nominal secondary voltage: 5 A or 1 A
  • Rated short-time thermal current, Ith: max 80 kA/1s (31,5 kA/3s)
  • Rated dynamic current, ldyn: max 200 kA
  • Rated continuous thermal current, Icth: 120 % In
  • Accuracy class – measurement: 0.2S, 0.2, 0.5S, 0.5, 1, 3
  • Overcurrent factor – measurement: FS 5, FS 10
  • Accuracy class – protection: 5P, 10P, PX
  • Overcurrent factor – protection: 5, 10, 15, 20, 25, 30
  • Nominal power: 5–60 VA
  • Nominal frequency: 50 Hz
  • Length creepage: 1322 mm
  • Weight: 80 kg
  • Thermal insulation class: E
  • Operation conditions: corresponds to temperature class -40/40 according to IEC 61869-1
  • Norma: IEC 61869-1, IEC 61869-2, GOST 15 150, GOST 1516.3-96

Drawing