Current instrument supporting transformer
CTS 25B Sch
Supporting instrument current transformers CTS 25B Sch are adapted for measuring and protecting internal medium voltage (MV) distribution equipment.
These transformers are designed for use in switchgear from SCHNEIDER ELECTRIC.
The secondary current value is either 5 A or 1 A, with the possibility of combination. Accuracy classes for measuring circuits are 0.2, 0.5, 0.2S, 0.5S, 1, 3, and for protective circuits are 5P, 10P, PX.
InquireDescription
The supporting instrument current transformers CTS 25B Sch are designed for measuring and protecting internal medium voltage distribution devices. They are suitable for use in switchgear from SCHNEIDER ELECTRIC.
The secondary current value is either 5 A or 1 A, with the option for combination.
Accuracy classes for measuring circuits include 0.2, 0.5, 0.2S, 0.5S, 1, 3, and for protective circuits, they are 5P, 10P, PX.
At the customer’s request, official verification can be provided. Other technical parameters can be consulted with the manufacturer.
CAUTION! WHEN OPERATING THE CTS 25B Sch TRANSFORMER, DISCONNECTION OF THE SECONDARY WINDING LEADS MUST BE AVOIDED.
Parameters
- Highest voltage for equipment: 24/25 kV
- Power frequency test voltage: 50 kV
- Lightning impulse test voltage: 125 kV
- Nominal primary current: 5 – 750 A
- Nominal secondary current: 5 A or 1 A
- Rated short-time thermal current, Ith: 31,5 kA
- Rated dynamic current, ldyn: 75 kA
- Rated continuous thermal current, Icth: 120 % In
- Accuracy class – measurement: 0.2S, 0.2, 0.5S, 0.5, 1, 3
- Overcurrent factor – measurement: FS 5, FS 10
- Accuracy class – protection: 5P, 10P, PX
- Overcurrent factor – protection: 5, 10, 15, 20, 25, 30
- Nominal power: 2,5 – 60 VA
- Nominal frequency: 50 Hz
- Weight: 30 kg
- Thermal insulation class : E
- Operation conditions: -5/40 according to ČSN EN 61869-1
- Standard: ČSN EN 61869-1, ČSN EN 61869-2, IEC 61869-1, IEC 61869-2, CSN EN 60044-1; IEC 60044-1