Current instrument supporting transformer
CTS 25X
Supporting current instrument transformers CTS 25X are designed for the measurement and protection of the distributing facilities of high voltage for inner settings.
The value of the secondary current is 5 A or 1 A with the possibility of combination. The classes of accuracy for the circuits of measurement are 0.2, 0.5, 0.2S, 0.5S, 1, 3, for the circuit of protection are 5P, 10P and PX. The transformers comply with the required class of accuracy within the values from 25% to 100% of rated load.
InquireDescription
Supporting current instrument transformers CTS 25X are designed for the measurement and protection of the distributing facilities of high voltage for inner settings.
The value of the secondary current is 5 A or 1 A with the possibility of combination. The classes of accuracy for the circuits of measurement are 0.2, 0.5, 0.2S, 0.5S, 1, 3, for the circuit of protection are 5P, 10P and PX. The transformers comply with the required class of accuracy within the values from 25% to 100% of rated load.
The limiting working current is 120% of IN, according to the agreement of producer and customer it is possible to supply other values, for example 200% of IN.
Transformers CTS 25X are constructed as transformers with single-turn or multi-turn primary winding. The up-to-date construction of these transformers allows the switching on the secondary side.
The secondary winding is wound on a magnetic core made from grain oriented sheets, or alloys of nickel, iron and copper (permalloy).
The number of cores can be from 1 to 2 according to the request of customer and according to the required parameters.
All active parts of transformer are compound-insulated with epoxy-mixture. This material performs both the electrical insulating and the mechanical functions.
The mounting position of transformers is arbitrary. Transformers are fixed by the means of four screws in the holes in the basic plate. The primary terminals of transformers are equipped with screws M12. We recommend use terminal ends corresponding to the used cross-section of the conductor for attaching to the secondary outlets. The secondary terminal plate is equipped with the cover with sealing screw. Inside, there is the set with jumpers and small screws for the possibility of earth connection and short circuiting of the wiring. (See “The Instructions for the mounting and operation”).
In cases, where the supplement for the older types of transformers (by various producers) is required, we supply instruments CTS 25X on the modified basic plates that have identical mounting spacing to spacing of the substituted types.
Transformers CTS 25X complied with all the tests according to IEC 61869-1, IEC 61869-2, IEC 61243-5, IEC 60068-2-11.
For the customer’s request we provide official calibration.
It is possible to consult other technical parameters with the producer.
Parameters
- Highest voltage for equipment: 24/25 kV
- Power frequency test voltage: 50 kV
- Lightning impulse test voltage: 125 kV
- Nominal primary current: 5 - 600 A
- Nominal secondary current: 5 A or 1 A
- Rated short-time thermal current, Ith: 31,5 kA
- Rated dynamic current, ldyn: 65 kA
- Rated continuous thermal current, Icth: 120 % In
- Accuracy class - measurement: 0.2S, 0.2, 0.5S, 0.5, 1, 3
- Overcurrent factor - measurement: FS 5, FS 10
- Accuracy class - protection: 5P, 10P, PX
- Overcurrent factor - protection: 5, 10, 15, 20, 25, 30
- Nominal power: 5 - 60 VA
- Nominal frequency: 50 Hz
- Length creepage: 245mm
- Weight: 19 kg
- Thermal insulation class: E
- Operation conditions: corresponds to temperature class -5/40 according to IEC 61869-1
- Standard: IEC 61869-1, IEC 61869-2, IEC 61243-5, IEC 60068-2-11