Support insulator

12 AN

The 12AN support insulators are intended for to be used in indoor systems operated at voltage levels of up to 12 kV.

The respective variants to the support insulator, identified by its type designation 12AN (i.e. 12AN -1, 12AN -2), differ each from the other in the location and dimensions of embedded elements.

The 12AN insulator complies with the requirements of IEC 60660, IEC 273, GOST 28739-90 standards.

The design may be varied according to the customer needs and requirements.

Inquire

Description

The 12AN support insulators are intended for to be used in indoor systems operated at voltage levels of up to 12 kV.

The respective variants to the support insulator, identified by its type designation 12AN (i.e. 12AN -1, 12AN -2), differ each from the other in the location and dimensions of embedded elements.

The 12AN insulator complies with the requirements of IEC 60660, IEC 273, GOST 28739-90 standards.

The design may be varied according to the customer needs and requirements.

An insulator is intented to isolate and insulate specific structural parts of an electric equipment operated at various voltage levels. The insulator allows for mechanical connection of parts on various voltage levels, without establishing a conductive bond between them.

Due to their properties the support insulators allow for safe construction of electric switchgear systems designed to withstand high mechanical stresses caused by short-circuit currents.

The body of a supporting insulator is made from epoxi resin which provideds for its heat, mechanical and electrical stability.

The embedded elements used to retain the screws are made from brass. The corresponding torque values are shown in Table 1.

Thread Torque [Nm]
M6 11,0
M8 27,5
M10 45,0
M12 63,0
M16 156,0
M20 204,0
M24 260,0

Recommended torque values [Nm] of threaded elements embedded in epoxi resin, with standardized type of surface treatment.

Read more

Parameters

  • Highest voltage for equipment: 7,5/12 kV
  • Power frequency test voltage: 20/28 kV
  • Lightning impulse test voltage: 60/75 kV
  • Nominal frequency: 50 Hz
  • Length creepage: 201,5 mm
  • Strength of bend: 8 kN
  • Weight: 0,7kg
  • Thermal insulation class: E
  • Operation conditions: operating temperature from -5 to + 40 °C
  • Standard: ČSN EN 60660, ČSN IEC 273, IEC 60660, IEC 273, GOST 28739-90
  • Order code: 600 000 476, 600 000 523

Drawing